尊龙凯时人生就是赢




产品中心 > GPH-WR12 KZ OEC-A20室内通信电源机柜
GPH-WR12 KZ OEC-A20室内通信电源机柜(1).png
  • GPH-WR12 KZ OEC-A20室内通信电源机柜(1).png

GPH-WR12 KZ OEC-A20室内通信电源机柜

GPH-WR12 KZ OEC-A20
室内通信电源机柜

特点

宽输入电压范围  

90VAC-300VAC宽输入电压范围,对恶劣电网适应性强,可保护电池。  


高效率输出  

整流器峰值效率高达97% ,休眠模式下整流器输出功率小于4W。  


灵活的监控与通信  

提供干接点 、RJ45/RS485/RS232/CAN接口及USB端口 ,支持LAN/RS485、LAN-SNMP、TCP/IP、CAN总线通信,可通过相关协议与监控后台实现通信,节省维护和初期投资成本。  


专业的监控与管理  

监控模块设计便于安装和维护 ,支持智能电池与整流器管理。


System Specifications

 

Electromagnetic compatibility

Comply with IEC61000 and EN 55032 standards.

Safety compatibility

Comply with IEC62368 standard.

Packaging and transportation

Comply with GB/T 2423.56-2006, IEC 60068-2-64:2008 standards.

Monitoring network mode

Provides dry contact, RJ45 ,RS485,RS232,CAN interfaces. LAN /RS485&RS232, LAN-SNMP, TCP/IP,CAN BUS can communicate with the monitoring background through relevant protocols1

Mean Time Between Failures (MTBF)

5.0×10 5h

Ac input 

Input mode

Three-phase five-wire (L1/L2/L3/N/PE)

220/380V AC power

Input voltage (phase-neutral)

Rated voltage: 220V

Voltage range: 90V-300V

Input frequency

Rated frequency: 50Hz

Frequency range: 45Hz-65Hz

Input power factor

At rated load, the input power factor is greater than or equal to 0.99.

AC lightning protection

30kA (8/20μs)

AC over-voltage protection

It is triggered when the input single-phase voltage is greater than the AC over-voltage protection point.

AC under-voltage protection

It is triggered when the input single-phase voltage is less than the AC under-voltage protection point.

Input over-current protection

It is triggered when the AC input air circuit breaker (or AC input contactor) provides over-current protection.

DC output

Rated output voltage

-53.5 V

Output voltage range

Continuous adjustment from-42 V to-58 V (via centralized monitoring unit)

Output rating

20kW (maximum configuration).

DC lightning protection

10 kA lightning protection

Cabinet voltage drop

≤  0.5V

Stabilization accuracy

≤  0.5%

Peak noise voltage

200 mV (bandwidth: 20 MHz)

Weighted noise voltage

2 mV

DC over-voltage protection

It is triggered when the output voltage is greater than the DC over-voltage protection point.

DC under-voltage protection

It is triggered when the output voltage is less than the DC under-voltage protection point.

Battery under voltage protection

It is triggered when the battery voltage is less than the protection point of voltage.

Structure

Cabling method

The cable enters and exits from the top of the cabinet

IEC IP

IP20.

Material

Hot-dip galvanized steel

The exterior color of the cabinet is light gray (color code: RAL 7035)

Size

600W600D1800H(mm)

Environment

Working temperature

-10 ℃ to +75 ℃

Relative to working humidity

5%-95% (non-condensable)

Storage temperature

-40 ℃ to +85 ℃

Relative to storage humidity

95% (non-condensable)

Air pressure

80 kPa to 106 kPa

Altitude

-100 to +2000 m: full power output

Load reduction above 2000m.





XML地图